Metal-Clad Cable with Nonmetallic Boxes?

Updated: May 5, 2023



There have been many questions regarding the use of Metal-Clad Cable in various occupancies as an alternative to Nonmetallic-Sheathed Cable, such as in residential dwelling applications. With those questions also came additional discussions regarding the bonding of the metallic sheathing (armor) and the overall compliance with the National Electrical Code [NEC]. In this article, we will attempt to answer all those questions.



Metal-Clad Cable [Type MC Cable], just as Nonmetallic-Sheathed Cable [Type NM-B], are UL/ANSI Listed wiring methods being utilized in all scopes of building wiring as permitted by the NEC. In fact, nothing within the NEC prohibits the use of Type MC in residential dwellings just like Type NM-B.


While Type NM-B is typically limited to Four (4) stories [Five (5) stories if sprinkled] depending on the type of construction being utilized, such as wood-framed construction, this is not an issue for Type MC Cable which has been well utilized in many mid-rise and high-rise buildings for decades. Type MC Cable is well suited for any Residential, Commercial, and Industrial applications provided it is installed in accordance with Article 330 of the NEC.


Focusing on residential applications, Type MC Cable, and the nonmetallic device boxes for a moment. The NEC permits Type MC Cable to be utilized in any application where Type NM-B is also permitted, such as all residential installations, such as single-family or multifamily dwellings. However, the usual question that comes up is about the device boxes being used. Can it be Plastic, Metal, or Both?


The easy answer is to always use a metal outlet or device box with armored cables, but let us address the harder question first, which is the one most installers ask. The use of Nonmetallic Boxes with Type MC Cable.


Nonmetallic Outlet Boxes, also referred to as PVC (Plastic) outlet or device boxes, with incorporated internal cable clamping systems, are listed, labeled, and identified for use only with nonmetallic-sheathed cables per UL Guide QCMZ. So, the installer could not “cut their own knock-out (hole)” into the device box and install a Type MC Cable. So, what about PVC (Plastic) device boxes with no clamps?


There are indeed Nonmetallic Outlet Boxes with ½” and ¾” knock-outs available but they are designed for use with Rigid Nonmetallic Raceways [Rigid PVC] or Electrical Nonmetallic Tubing [ENT]. When these types of outlet boxes are encountered, they will state the wiring methods permitted to be used with them.


The next question would be, is there anything within the NEC that would permit a metal armored cable, such as Type MC, to be connected to a nonmetallic box? Yes, but we must examine the NEC to fully understand what is permitted.


“314.3 Nonmetallic Boxes.

Nonmetallic boxes shall be permitted only with open wiring on insulators, concealed knob-and-tube wiring, cabled wiring methods with entirely nonmetallic sheaths, flexible cords, and nonmetallic raceways.


Exception No. 1: Where internal bonding means are provided between all entries, nonmetallic boxes shall be permitted to be used with metal raceways or metal-armored cables.


Exception No. 2: Where integral bonding means with a provision for attaching an equipment bonding jumper inside the box are provided between all threaded entries in nonmetallic boxes listed for the purpose, nonmetallic boxes shall be permitted to be used with metal raceways or metal-armored cables.”


At first glance, it appears that nonmetallic boxes can only be used with entirely nonmetallic sheaths, such as Type NM-B and UF-B, and nonmetallic raceways, such as Rigid PVC or ENT as previously discussed. However, we must look at the “EXCEPTIONS” to the general rule to fully understand what is and what is not being permitted, and of course here is where it can get tricky for those unsavvy in the NEC.


In our case ( See Image Below), Exception # 1 says that if the installer chooses to install Type MC Cable to a nonmetallic box, that is NOT limited to use with Type NM-B and Type UF-B or Type ENT, the installer shall provide some form of internal bonding means, such as a bonding bushing with a bonding jumper(s), to ensure that all the equipment grounding conductors within the nonmetallic box remain connected together and mutually bonded to the armor. This would also apply to the use of any “Smart Ground” Type MC products as well since the armor is being used as an equipment grounding conductor.

As for Exception # 2 which is for manufacturers who build a specific integral means within the nonmetallic box itself for interconnection of equipment bonding jumpers (or equipment grounding conductors), such as those we see in swimming pool boxes, which are typically nonmetallic.


As a Codes and Standards recommendation, when it comes to using Type MC Cable, the best practice is to always use metallic boxes and appropriately UL/ANSI listed fittings (connectors). The armor is bonded to the metal fitting and ultimately connected to the metal box which completes the bonding requirements for these products. Once the equipment grounding conductor is attached (terminated) to the metal box, inside the box itself, the process is complete.


Hope this helps answer any of those questions on the use of Metal-Clad Cable in Residential installations as well as the use with both nonmetallic boxes and metallic boxes with armored products for a code compliant, reliable, and ultimately safe installation.


By Paul W. Abernathy, CMECP®

CEO, President, and Founder




For more information on our Electrical Training Products, such as our Residential, Commercial, Industrial, Grounding and Bonding, and Electrical Exam Preparation Courses visit https://fasttraxsystem.com


Paul Abernathy, CMECP® | CEO & President

Electrical Code Academy, Inc. | www.FastTraxSystem.com 3913 Edward Drive., McKinney, TX 75071 Office: 214-945-0653


Visit Fast Trax® Tube- Video Platform for Electricians Visit Fast Trax® Chat - NEC® Support Live Chat Visit The Sparky Hub™ - Online Electrical Message Board Need Project & Customer Management Software? - PPM Butler™ Need an Online Business or Personal Profile? - Profile Butler™ Need Quick and Easy Online Accounting Software? - Accountant Butler™


Office Hours: M-F 8:00 am - 5:00 pm CST


Disclaimer: Our company accepts no liability for the content of this email and/or associated website(s), or for the consequences of any actions taken on the information provided in this email or posted on any company websites.


If you are not the intended recipient you are notified that disclosing, copying, distributing, or taking any action in reliance on the contents of this information is strictly prohibited.



6,982 views3 comments

Electrical Code Academy, Inc.

 

* NOTICE: NEC or National Electrical Code are Registered Trademarks of the National Fire Protection Association and are used for educational purposes only. We are not associated or affiliated with the NFPA, also known as the National Fire Protection Association. Electrical Code Academy, Inc. doesn't offer codes and standards publications or software on the NEC, NFPA70, or the National Electrical Code. Electrical Code Academy, Inc. provides educational and motivational speaking, education, and consulting services on how to use, apply and interpret the National Electrical Code. The use of the phrase Master The NEC is for educational purposes only and in no way represents a relationship with the NFPA.

 

Certified Master Electrical Code Professional®, Fast Trax® and CMECP® are Federally Protected Trademarks of Electrical Code Academy, Inc.

Electrical Code Academy Privacy Notices
  • Pinterest
  • LinkedIn
  • Blogger
  • Instagram
  • YouTube
  • Twitter
  • Facebook
  • Spotify
  • Deezer
All Sales Final - No Refunds or Cancellations on Digital Courses/Online-Courses Purchased.
-All Courses are E-Mailed within 1-5 Business Days-
-Website Terms & Conditions of Use-

© 2021 by Electrical Code Academy, Inc.

bottom of page